9PX11KiBP Topology On-line double conversion with PFC (Power Factor Correction) system Configuration Rack/Tower Part Number 9PX11KiBP Rating (VA/Watts) 11000/10000 Dimensions (H x W x D, mm) 440 x 260 x 700 Weight (kg) 86 Warranty 2 years warranty Electrical Input Connection Hardwired - see manual for terminal block layout Hardwired - example layout only Input Voltage Range 176-276V without derating (up to 100–276V with derating) Nominal Voltage 200/208/220/230/240/250V Frequency 50/60 Hz autoselection Frequency Range 40-70 Hz Short Circuit Current 150 A THDI <5% Electrical Output Voltages 200/208/220/230/240/250V +/– 1% Voltage THD < 2% Output Receptacles (4) IEC-320-C19 Hardwired - see manual for terminal block layout Hardwired - example layout only Overload Capacity 102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms Efficiency (Normal Mode) Up to 95% in Online mode, 98% in Hi-Efficiency mode Output Frequency 50/60 Hz autoselect, frequency converter as standard Load Crest Factor 3:1